Isa standards

From claude-dev-suite/claude-dev-suite · View interactive version

Isa standards is an AI agent skill from the GitHub repository claude-dev-suite/claude-dev-suite. ISA-5.1 tag naming, ISA-88 batch control, ISA-95 enterprise integration, ISA-18.2 alarm management, and ISA-101 HMI standards reference. Use when working with instrument tags, naming conventions, or plant hierarchy.

How to use this skill

Skill file

ISA Standards Reference for Industrial Automation

ISA-5.1: Instrumentation Symbols and Identification

Tag Number Structure

[Area].[Functional ID].[Loop Number][Suffix]

Functional ID = [First Letter: measured variable] + [Succeeding Letters: function/modifier]

Examples from project:
  11301.PDI.076A   = Area 11301, Pressure Differential Indicator, loop 076, suffix A
  11301.SALL.020A  = Area 11301, Speed Alarm Low-Low, loop 020, suffix A
  11301.FIC.056A   = Area 11301, Flow Indicating Controller, loop 056, suffix A
  11301.CLWW.1A1   = Area 11301, Conveyor (equipment tag), unit 1A1

First Letter (Measured/Initiating Variable)

| Letter | Variable | As Succeeding Letter |

|--------|---------|---------------------|

| A | Analysis (pH, O2, conductivity) | Alarm |

| B | Burner, Combustion | User's choice |

| C | User's Choice | Control |

| D | User's Choice | Differential |

| E | Voltage (EMF) | Sensor/Element |

| F | Flow Rate | Ratio/Fraction |

| G | User's Choice | Glass/Gauge |

| H | Hand (Manual) | High |

| I | Current (Electrical) | Indicate |

| J | Power | Scan |

| K | Time, Schedule | Time Rate of Change |

| L | Level | Light/Low |

| M | User's Choice | Middle/Intermediate |

| N | User's Choice | User's choice |

| O | User's Choice | Orifice/Restriction |

| P | Pressure, Vacuum | Point (test) |

| Q | Quantity | Totalize/Integrate |

| R | Radiation | Record |

| S | Speed, Frequency | Switch/Safety |

| T | Temperature | Transmit |

| U | Multivariable | Multifunction |

| V | Vibration, Mechanical Analysis | Valve/Damper |

| W | Weight, Force | Well/Probe |

| X | Unclassified | Unclassified |

| Y | Event, State, Presence | Relay/Compute |

| Z | Position, Dimension | Actuator/Driver |

Common Tag Combinations

Flow:

FE (element), FT (transmitter), FI (indicator), FIC (indicating controller), FCV (control valve), FAH (alarm high), FAL (alarm low), FAHH (alarm high-high), FALL (alarm low-low), FSH (switch high), FSL (switch low), FQI (quantity indicator/totalizer), FR (recorder)

Level:

LT, LI, LIC, LCV, LAH, LAL, LAHH, LALL, LSH, LSL, LSHH, LSLL, LG (gauge glass)

Pressure:

PT, PI, PIC, PCV, PAH, PAL, PAHH, PALL, PDI (differential indicator), PDIC, PDT, PSH, PSL, PSV (safety valve), PG (gauge)

Temperature:

TE (element), TT, TI, TIC, TCV, TAH, TAL, TSH, TSL, TR (recorder), TW (thermowell)

Position/Valve:

ZT (position transmitter), ZI, ZIC, ZAH (open alarm), ZAL (closed alarm), ZSH (open switch), ZSL (closed switch), ZSHH, ZSLL

Speed:

ST, SI, SIC, SAH, SAL, SAHH, SALL

Current (Electrical):

II (current indicator), IIC (current indicating controller), IAH, IAHH

Vibration:

VI (vibration indicator), VAH, VAHH

Equipment Tags (Non-ISA, Plant-Specific)

| Code | Equipment Type | Example |

|------|---------------|---------|

| K | Kiln/Equipment | 11301.K.9 |

| N | Pump | 11301.N.3A |

| F | Feeder | 11301.F.4 |

| WG | Weighing belt | 11301.WG.8 |

| SR | Screen/Separator | 11301.SR.9A |

| CL/CLWW | Conveyor (weigh) | 11301.CLWW.1A1 |

| KC | Crusher | 11301.KC.F.4 |

| EL | Elevator | 11301.EL.AA |

| Z | Silo/Storage | 11301.Z.2A |

Tag Naming Variations by Region/Vendor

| Convention | Format | Example |

|-----------|--------|---------|

| ISA Pure | FIC-101A | American standard |

| European (this project) | 11301.FIC.101A | Area.Function.LoopSuffix |

| Siemens/KKS | +FIC101A= | German power plant standard |

| DeltaV path | FIC-101A/PV | With parameter path |

| Honeywell | FIC101A.PV | With point parameter |


ISA-88: Batch Control (S88)

Physical Model Hierarchy

Enterprise
  +-- Site
       +-- Area
            +-- Process Cell
                 +-- Unit
                      +-- Equipment Module (EM)
                           +-- Control Module (CM)

Mapping to DCS Engineering

| ISA-88 Concept | DCS Implementation | Example |

|----------------|-------------------|---------|

| Control Module | Function block instance | Motor block, valve block, PID loop |

| Equipment Module | Sequence/SFC | Reactor filling sequence |

| Unit | Process unit with sequences | Reactor R-101 |

| Process Cell | Group of units | Production Line A |

Control Module Types (Standard Templates)


ISA-95: Enterprise-Control Integration

Equipment Hierarchy (extends ISA-88 upward)

Enterprise > Site > Area > Work Center > Work Unit

Relevance to Tag Naming

Tags should encode the hierarchy. Example: 11301.FIC.056A


ISA-18.2: Alarm Management

Alarm Priority Distribution (Guideline)

| Priority | Percentage | Response Time |

|----------|-----------|--------------|

| Critical (1) | ~5% | Immediate |

| High (2) | ~15% | < 5 minutes |

| Medium (3) | ~30% | < 30 minutes |

| Low (4) | ~50% | Next round |

Alarm Tag Properties for Bulk Engineering

Each alarm tag requires: Priority, Setpoint (limit), Deadband, On-delay, Off-delay, Alarm class (Process/Safety/Equipment), Shelving capability.

Naming Convention for Alarms

{Area}.{Variable}{AlarmType}.{Loop}{Suffix}
  PAH  = Pressure Alarm High
  PAHH = Pressure Alarm High-High
  PAL  = Pressure Alarm Low
  PALL = Pressure Alarm Low-Low

In Freelance EAM: XA1 = primary alarm, XA2 = secondary alarm

ISA-101: Human Machine Interfaces

Display Hierarchy

| Level | Name | Content | Quantity |

|-------|------|---------|---------|

| 1 | Plant Overview | Entire plant, KPIs | 1-3 |

| 2 | Area Overview | One process area | 5-20 |

| 3 | Unit Detail | One unit operation | 20-100 |

| 4 | Faceplate/Detail | One control loop | Auto-generated |

High-Performance HMI Principles

Use this skill with your AI agent: Open on Skill Issue to copy, download, or add to your library. Works with Claude, ChatGPT, Gemini, Cursor, Windsurf and more.