Neqsim process safety is an AI agent skill from the GitHub repository equinor/neqsim. Process safety methodology - barriers, PSFs/SCEs, HAZOP, LOPA, SIL per IEC 61511, integrated safety response, change revalidation, bow-tie, risk matrix, TR3001 overpressure studies, trapped-liquid rupture. USE WHEN: a task needs barrier registers, hazard identification, LOPA, SIF SIL assignment, ESD

How to use this skill

Skill file

NeqSim Process Safety Skill

Systematic hazard identification, layer-of-protection analysis (LOPA), and

safety-integrity-level (SIL) determination — the quantitative half of process

safety that complements depressurization (neqsim-dynamic-simulation) and relief

sizing (neqsim-relief-flare-network).

When to Use

including PFP demand and source-term handoff

contingencies, select the governing case, size the PSV, and check TR3001 / API

521 compliance

verified API 2000 demand and device evidence

Standards: IEC 61508, IEC 61511, CCPS LOPA Guidelines, API 521 / ISO 23251, API 520, API 2000, TR3001, ASME VIII Div 1 (UG-125), ASME B31.3/B31.4, ASME B16.5, API 754, NORSOK Z-013.

For API 2000, route to Api2000TankVentingScreeningKernel. Require caller-controlled licensed

demand factors/cases, externally rated capacities, consistent gas reference conditions, tank

pressure/vacuum limits, and evidence attestations. Do not relabel FireProtectionDesign, generic

PSV sizing, or an adequate screen as API tank-vent sizing or conformity.

Subsea tie-back pressure protection

For a well-to-platform case, use the executable pressure-protection study.

Record each zone's pressure datum and allowable transient pressure, valve feedback, actual boundary transfers and refinement sensitivity.

Use the verifier's adjacent 60→120 and 120→240 cell comparisons for the synthetic case. Carry

the resulting numerical verdict and the drawing findings into the study. Compare the two end

stations and the fixed riser-base station, retaining the zone substep maxima and the pressure

front, trip and seat times. Use --benchmark for a synchronized independent reference from the

same fixture. Carry a HOLD when a matched reference is missing. Evaluate channel independence

and reliability with project data.

A TwoFluidPipe blocked-outlet or HIPPS run must enable setEnableCoupledPressureMomentum(true) and

setEnableInterfacialPressure(true). Without them the pressure behind a CLOSED boundary stays flat while mass

accumulates, and the study silently shows no overpressure (TwoFluidPipeLinePackingTest; runTransient now warns).

Check the fortified-zone volume between the HIPPS and the first closable downstream valve: in a 12-inch, 300 t/h,

SITHP 275 bara tie-back (measured 2026-11-21), a valve closing 40 m downstream drove the line to SITHP before 12 s

HIPPS valves seated, while a full 15.6 km line took about 32 min to reach the 180 barg trip (remeasured 2026-11-22

with the frozen-composition property update, which is the default; with setFrozenCompositionDensityUpdate(false) the

same run shows 90-130 bar steps at the closed riser top that are not pressure peaks; with the default, steps of up to

13 bar remain there, so take the trip time from the inlet pressure).

Method 0b — Trapped-Liquid Fire Rupture Screening

Load neqsim-trapped-liquid-fire-rupture when a safety study concerns a

blocked-in liquid-filled pipe segment exposed to fire, no pressure relief, PFP

endurance, flange/pipe rupture, or a Word/HTML study report based on P&IDs/STID,

line lists, material certificates, and fire documents.

Recommended sequence:

  1. Retrieve the evidence package with the enterprise skill enterprise-stid-document-retrieval (or supplied documents): P&ID/STID,

line list, piping spec, material certificate, flange/bolt/gasket data,

fire-zone/PFP documents, relief basis, and design basis.

  1. Extract a structured segment list with neqsim-technical-document-reading:

isolation boundary, line numbers, fluid, P/T, ID, wall thickness, length,

material grade, flange class, fire basis, PFP endurance, relief availability,

acceptance criteria, and evidence gaps.

  1. Use TrappedInventoryCalculator to calculate trapped mass and volume.
  2. Use FireExposureScenario, MaterialStrengthCurve, and

TrappedLiquidFireRuptureStudy to calculate event times and limiting mode.

  1. Convert outputs to SafetySystemDemand for PFP checks and to

SourceTermResult for consequence handoff if rupture is predicted.

  1. Report all screening defaults as assumptions. Missing project data must stay

visible in an evidence/gaps register.

Method 0 — Evidence-Linked Barrier Register

Use BarrierRegister, SafetyCriticalElement, SafetyBarrier, PerformanceStandard,

and DocumentEvidence when agents read technical documentation and need a traceable

handoff into LOPA, SIL, bow-tie, or QRA.

Recommended sequence:

  1. Extract DocumentEvidence from P&IDs, C&E charts, SRS, SIL verification reports,

inspection reports, vendor datasheets, and operating procedures.

  1. Build PerformanceStandard objects for each PSF/SIF/SCE function with target PFD,

availability, proof-test interval, response time, and acceptance criteria.

  1. Build SafetyBarrier objects with type, status, PFD/effectiveness, equipment tags,

hazard ids, owner, evidence, and performance-standard links.

  1. Group barriers under SafetyCriticalElement records using process equipment tags.
  2. Run MCP runBarrierRegister to get validation findings plus lopaHandoff,

silHandoff, bowTieHandoff, and qraHandoff blocks.

Credit rule: do not claim LOPA credit unless the barrier is AVAILABLE, has a valid

PFD, has a linked performance standard, and has traceable evidence. Missing evidence

must remain visible as a validation finding.

Method 1 — HAZOP Guidewords

Apply the 7 standard guidewords to each design intent at every node:

| Guideword | Deviation example | Typical cause |

| --------- | ----------------------------------------- | ----------------------------------- |

| NO | No flow to separator | Pump trip, blocked inlet |

| MORE | More pressure in V-100 | PCV stuck open, inlet surge |

| LESS | Less level in V-100 | LCV stuck open, drain leak |

| AS WELL AS | Water carryover in gas | Demister flooding, wave action |

| PART OF | Wrong composition fed | Crossover from neighbouring train |

| REVERSE | Reverse flow from compressor | Check valve failure |

| OTHER THAN | Maintenance with line live | Procedural / isolation failure |

Output as a HAZOP worksheet table; each row → candidate LOPA scenario.

For automated studies from STID/P&ID documents and NeqSim process simulations,

use MCP runHAZOP. It accepts a standard runProcess JSON model plus optional

document-extracted nodes, safeguards, evidence references, selected failure

modes, and a barrierRegister. The runner executes generated safety scenarios

on copied ProcessSystem models and returns IEC 61882 rows, simulation evidence,

quality gates, barrier-register handoff, and report markdown. See

docs/safety/automated_hazop_from_stid.md.

For a P&ID Safety Analyser / AI-HAZOP front-end that quantifies one deviation at

a time, use MCP runHazopScenario (backed by

neqsim.mcp.runners.HazopScenarioRunner). It accepts a runProcess JSON model

plus an optional guideWord / parameter / nodeTag filter and a limits

policy, and returns a stable schemaVersion "1.0" response where every finding

carries a computedValue, designLimit, verdict (PASS / EXCEEDS /

NOT_EVALUATED), standardReference, and a limitBasis provenance string

(HazopConsequenceFinding#getLimitBasis()) so a reviewer can see whether the

limit is a data-sheet value or a screening default. Equipment design limits

(neqsim.process.mechanicaldesign.DesignConditions) round-trip into DEXPI as a

GenericAttributes Set="DesignConditions" group, and blocked-outlet MORE

PRESSURE deviations can be screened with

neqsim.process.safety.depressurization.BlockedOutletOverpressureAnalyzer. See

docs/safety/ai_hazop_input_format.md for the full input-data format.

Method 1b — Quantify the governing deviations of a separator node

A guide-word grid on its own is not decision-grade. For a separation node, four

deviations carry the risk; each maps to a class that turns the qualitative row

into a number against a data-sheet limit:

| Guideword / parameter | Class | Standard |

| --- | --- | --- |

| MORE FLOW / MORE LEVEL (carryover) | Souders-Brown K = v_gas / sqrt((rho_l-rho_g)/rho_g) from the run ProcessSystem; SeparatorMechanicalDesign.setFromExistingDesign(id, lTanTan, wallThickness) to pin the as-built geometry | NORSOK P-002, GPSA |

| MORE PRESSURE (fire) | neqsim.process.safety.overpressure.FireCaseRelief | API 521 §4.3 |

| MORE PRESSURE (blocked outlet) | neqsim.process.util.fire.ReliefValveSizing.calculateRequiredArea on the full inlet gas rate; BlockedOutletOverpressureAnalyzer for the transient | API 520 Part I, API 521 §4.4.2 |

| LESS LEVEL (gas blow-by) | neqsim.process.safety.blowby.GasBlowbyAnalyzer | API 521 §4.4.7 |

| LESS TEMPERATURE (MDMT) | neqsim.process.safety.depressurization.DepressurizationSimulator + result.meetsMDMT(mdmtK) | API 521 §5.20, ASME VIII UCS-66 |

Three heuristics that repeatedly decide the outcome:

The fire case only vents vapour generated from the wetted area, while a blocked

gas outlet must vent the whole inlet gas rate. Always size both and state which

governs — a 10× difference in required orifice area is normal.

set purely by the open area of the level-control valve, not by downstream

pressure. When the valve Cv is unknown, present a 2″–8″ equivalent-diameter

sensitivity rather than picking one number.

(setWall(mass, area, cp, htc)); several hundred tonnes of steel keeps the

metal near ambient. The cold spot is the BDV/PSV tail pipe — check it with an

isenthalpic PHflash of the gas down to flare pressure, not with the vessel

temperature.

Carryover margin scales as 1/(1-level), so report the utilisation as a level

sensitivity — it converts "verify the HH trip" into a numeric trip setpoint.

Method 1c — Run the studies on every safeguard of a generated P&ID

When a P&ID was synthesized from the process (PidDesignSynthesizer), run

PidSafetyStudies.run(pid, process, PidSafetyStudies.Policy.screening()) after

PidStandardConnectionProposals.complete(...). It applies the Method 1b calculations to

every proposed PSV (blocked outlet, fire, gas blow-by through upstream liquid valves),

sizes each BDV by dynamic blowdown to the API 521 target, sums the flare load, places

trip set points between operating and relief limits, sets NOG 070 SIL targets and screens

PFDavg. Results land on the P&ID elements, the drawings, DEXPI and the HAZOP preparation

(quantifiedSafeguardEvidence). The blowdown minimum temperature is the fluid

temperature without wall heat capacity: treat BLOWDOWN_LOW_TEMPERATURE as a prompt

for the wall/tail-pipe check above. Report every finding; reliability data are screening

values (docs/process/safety/pid-safety-studies.md).

Method 2 — LOPA Worksheet

Use CODE0 to compute residual frequency:

import neqsim.process.safety.risk.sis.LOPAResult;

LOPAResult lopa = new LOPAResult();
lopa.setScenarioName("V-100 overpressure during compressor surge");
lopa.setInitiatingEventFrequency(0.1);   // /yr — surge event
lopa.setTargetFrequency(1.0e-5);         // /yr — tolerable for safety SIF

// Independent Protection Layers (each must be IEC 61511 IPL-eligible)
lopa.addLayer("BPCS pressure control",     0.10, 0.1,    0.01);
lopa.addLayer("Operator response (alarm)", 0.10, 0.01,   0.001);
lopa.addLayer("PSV @ design",              0.01, 0.001,  1.0e-5);

System.out.println(lopa.toVisualization());
System.out.println("Target met? " + lopa.isTargetMet());
System.out.println("Required additional SIL: " + lopa.getRequiredAdditionalSIL());

IPL eligibility rules (IEC 61511):

Method 2b — Traceable HAZOP/LOPA to draft SRS

Use LopaScenarioDefinition, ProtectionLayerDefinition, and HazopLopaSrsWorkflow when an

approved HAZOP row and user-supplied risk basis need a machine-readable handoff into SRS drafting.

The workflow credits a layer only when independence from the initiating event and other layers,

specificity, auditability, proof-test/inspection interval, and a controlled evidence reference are

all declared. Ineligible safeguards remain visible but receive no frequency reduction.

If a risk gap remains, the result creates a SafetyRequirementSpecificationDraft carrying the

HAZOP node/deviation, LOPA reference, SIF tag, trip, safe state, response time, voting, proof-test,

reset, and bypass requirements. The draft is always REVIEW_REQUIRED and never fit for construction.

No draft is created when credited existing layers meet the supplied target.

After accountable HAZOP, LOPA, and SRS approval, hand the approved inputs to

SafetyFunctionDesign, reliability/degraded-mode assessment, and closed-loop transient

verification. See docs/process/safety/hazop-lopa-srs-handoff.md.

Method 3 — SIL Determination

After LOPA tells you a SIL is needed, verify with CODE0:

import neqsim.process.safety.risk.sis.SafetyInstrumentedFunction;
import neqsim.process.safety.risk.sis.SafetyInstrumentedFunction.SIFCategory;

SafetyInstrumentedFunction sif = SafetyInstrumentedFunction.builder()
    .id("SIF-001")
    .name("HIPPS on V-100")
    .description("Close XV-1001A/B on PT-1001 high-high (2oo3)")
    .sil(2)                           // claimed
    .pfd(5.0e-3)                      // PFD_avg from supplier verification
    .testIntervalHours(8760.0)        // 1-year proof test
    .mttr(8.0)
    .architecture("2oo3")
    .category(SIFCategory.HIPPS)
    .initiatingEvent("Compressor surge → backflow")
    .safeState("XV closed, V-100 isolated")
    .build();

double rrf = sif.getRiskReductionFactor();    // 1/PFD
int silAchieved = sif.getSil();

SIL bands (IEC 61508):

| SIL | PFDavg | RRF |

| --- | ------------------- | --------------- |

| 1 | 1e-2 to 1e-1 | 10–100 |

| 2 | 1e-3 to 1e-2 | 100–1000 |

| 3 | 1e-4 to 1e-3 | 1000–10000 |

| 4 | 1e-5 to 1e-4 | 10000–100000 |

Method 3b — NOG 070 SIL Catalogue (Norwegian shelf typical SIFs)

For Norwegian-shelf projects, the NOG 070 (070 Norsk olje og gass) guideline

gives pre-determined minimum SIL for typical SIFs — use

Nog070SilCatalogue / Nog070SilDetermination to look up the minimum and

verify the achieved SIL from PFD:

import neqsim.process.safety.risk.sis.nog070.Nog070SifType;
import neqsim.process.safety.risk.sis.nog070.Nog070SilDetermination;

// HIPPS minimum is SIL 3; PFD 1e-4 achieves SIL 3 → compliant
Nog070SilDetermination r =
    Nog070SilDetermination.evaluate(Nog070SifType.HIPPS_PIPELINE, 1.0e-4);
int achieved = r.getAchievedSil();   // 3
int minimum  = r.getMinimumSil();    // 3
boolean ok   = r.isCompliant();      // true
String json  = r.toJson();

Nog070SifType includes HIPPS_PIPELINE, ESD_SUBSEA_ISOLATION (SIL 3),

BLOWDOWN_HYDROCARBON_SEGMENT, PSD_PROCESS_SEGMENT (SIL 2), and CUSTOM

(supply an explicit minimum via the 3-arg evaluate). Verified by

Nog070SilCatalogueTest.

Method 3c — ESD Response-Time Budget (NOG 070 / IEC 61511)

Verify the full detection → logic → final-element chain fits the allowable ESD

response time with EsdResponseTimeSimulator:

import neqsim.process.safety.esd.EsdResponseTimeSimulator;
import neqsim.process.safety.esd.EsdResponseTimeSimulator.EsdResponseTimeResult;

EsdResponseTimeResult res = new EsdResponseTimeSimulator()
    .setSifTag("ESD-1234")
    .addDetection("PT-1001 high-pressure", 1.0)         // [s]
    .addLogic("Logic solver scan + 2oo3 vote", 0.5)     // [s]
    .addValve("ESDV-2001", 0.5, 8.0)                    // command delay + stroke [s]
    .setAllowableResponseTimeS(15.0)
    .evaluate();

double total = res.getTotalResponseTimeS();   // 10.0
double margin = res.getMarginS();             // 5.0
boolean within = res.isWithinBudget();        // true

Verified by EsdResponseTimeSimulatorTest.

Method 3d — Closed-loop SIF transient verification

Use ClosedLoopSafetyFunction inside a DynamicSafetyScenario when a response-time budget must

be demonstrated against the process model rather than summed from prepared durations. Bind every

SafetyFunctionChannel to the isolated process copy, select the SRS voting pattern, then pass an

existing ESDLogic, HIPPSLogic, or other ProcessLogic as the final-element sequence.

Recommended sequence:

  1. Configure and solve the normal process case.
  2. Apply one controlled initiating event on the scenario copy.
  3. Bind sensor channels to live process properties, including response delay and an explicit

FaultMode for degraded cases.

  1. Use the SRS MooN VotingPattern and logic-solver delay.
  2. Define dynamic criteria for the actual safe state and deadline, such as ESD valve opening,

protected pressure, compressor state, or depressuring pressure.

  1. Review DynamicSafetyScenarioResult.getLogicEvidence() for readings, bypass/fault state, vote

time, final-element actuation, and trace; do not approve from the boolean verdict alone.

See docs/process/safety/closed-loop-sif-verification.md. This simulation evidence does not infer

SIL or approve the SRS; hand the result to the SIL/LOPA and engineering-approval workflow.

Method 3e — Reliability uncertainty and degraded/maintenance modes

After the deterministic SafetyFunctionDesign screen, use SafetyFunctionReliabilityStudy to

propagate evidence-based failure-rate, diagnostic-coverage, proof-test, repair-time, beta, and bypass

uncertainty. Always provide a fixed seed and retain P10/P50/P90 PFDavg/PFH, target-met probability,

iteration count, distributions, and their data sources in the verification package.

Use SafetyFunctionOperatingMode plus SafetyFunctionDegradedModeAssessment before evaluating a

bypass or maintenance state. Record every unavailable, forced-trip, or under-repair channel, actual

proof-test age, authorization reference, compensating measure, elapsed duration, and maximum duration.

The effective architecture (for example 2oo3 to 2oo2) is a demand-capability screen, not permission to

preserve the SIL claim or continue operation.

Handoff the assessed mode back to the closed-loop scenario workflow to verify the physical safe state.

See docs/process/safety/sif-reliability-and-degraded-modes.md.

Method 3f — Integrated facility safety response

Use FacilitySafetyResponseStudy after the individual engines have executed when one review package

must join closed-loop ESD/HIPPS evidence, compressor anti-surge trip demand and observed response,

PSV/concurrency results, transient blowdown/flare results, and controlled process limits such as MDMT

or hydrate margin. Supply the actual DynamicSafetyScenarioResult and

CoupledReliefBlowdownFlareResult; the facility study embeds their maps and must not duplicate their

physics.

For HIPPS or PSD response on a TwoFluidPipe tie-back, compare zone allowables against the

substep pressure envelope (TwoFluidPipe.getLastIntervalPeakPressureProfile), not end-of-step

samples, and set the pipe CFL to 0.25 for riser-base fallback. The measurement and refinement

recipe are in the neqsim-dynamic-simulation skill and

examples/production-decision/tieback-protection.md.

Capture compressor response with CompressorTripResponse.capture(...). AntiSurge.shouldTrip() is

the demand signal; separately record whether the trip was observed, its response time, allowable

deadline, and evidence reference. Add each minimum or maximum with ProcessSafetyConstraint and a

controlled source reference.

Treat isTechnicallyAcceptable(), isEvidenceComplete(), and isReadyForEngineeringReview() as

review gates, never approval. Inspect getFindings() and embedded engine results, then obtain the

accountable process-safety, rotating-equipment, flare, piping, and mechanical approvals. See

docs/process/safety/integrated-facility-safety-response.md.

Method 3g — Safety change impact and revalidation

Use SafetyStudyRevalidationPlanner with the canonical EngineeringGraph and a controlled

ModelChangeEvent. Tag safety lifecycle nodes with the safetyStudyType property and an accepted

type: HAZOP, LOPA, SRS, SIF_RELIABILITY, SIF_DYNAMIC_VERIFICATION,

RELIEF_BLOWDOWN_FLARE, or FACILITY_RESPONSE. Express dependencies with normal graph edges; do not

create a separate safety dependency register.

The planner delegates propagation to GeneralizedImpactAnalyzer, then adds type-specific work,

propagation paths, reason edges, stale approvals, unresolved subjects, and cycle findings. Every task

starts incomplete. Close it and restore approval through project MOC/document control.

Method 3h — Independent safety verification benchmarks

Use SafetyVerificationBenchmarkSuite to qualify the versioned SIF PFDavg, LOPA residual-frequency,

and dynamic-response methods against externally supplied values. Declare the source class, controlled

reference, dataset revision, tolerances, and independent-review record. A

REGRESSION_BASELINE is useful but deliberately cannot qualify as independent evidence.

Do not call an expected value independent merely because it was entered by a different user. Verify

the calculation or published/vendor/CAE source, assumptions, units, method version, and review record

outside the code. A passing suite qualifies the controlled implementation/case set, not the project

design or SIL target. See docs/process/safety/safety-change-revalidation-and-benchmarks.md.

Method 4 — Bow-Tie Analysis

Use CODE0

import neqsim.process.safety.risk.bowtie.BowTieModel;
import neqsim.process.safety.risk.bowtie.BowTieModel.Threat;
import neqsim.process.safety.risk.bowtie.BowTieAnalyzer;

BowTieModel bt = new BowTieModel("Loss of containment — V-100 gas phase");
bt.addThreat(new Threat("Overpressure", 0.1));
bt.addThreat(new Threat("Corrosion-induced rupture", 0.01));
// preventive barriers reduce threat → top-event frequency
// mitigative barriers reduce consequence severity

BowTieAnalyzer analyzer = new BowTieAnalyzer(bt);
double topEventFreq = analyzer.calculateTopEventFrequency();

Export to SVG with BowTieSvgExporter for the report.

Method 5 — 5×5 Risk Matrix

Use CODE0 to score and rank scenarios per ISO 31000 / NORSOK Z-013.

Frequencies × Consequence categories → ALARP / intolerable / broadly acceptable bands.

Method 6 — API RP 14C SAFE Chart (offshore device coverage)

Auto-enumerate process equipment and check that each has its API RP 14C–required

protective devices (PSH/PSL/LSH/LSL/PSV …) with Api14cSafeChartBuilder:

import java.util.EnumSet;
import neqsim.process.safety.api14c.Api14cSafeChartBuilder;
import neqsim.process.safety.api14c.Api14cDeviceType;

// declarePresent(...) lists the devices actually installed, then build(process)
Api14cSafeChartBuilder chart = new Api14cSafeChartBuilder()
    .declarePresent("HP separator",
        EnumSet.of(Api14cDeviceType.PSH, Api14cDeviceType.PSV))
    .build(process);

boolean complete = chart.isComplete();   // false → missing devices
chart.getGaps();                         // equipment with missing required devices
String md = chart.toMarkdown();          // SAFE chart table
String json = chart.toJson();

buildAssumingComplete(process) enumerates equipment and assumes full coverage

(useful for generating the SAFE chart skeleton). Equipment categories come from

Api14cEquipmentCategory (e.g. PRESSURE_VESSEL). Verified by

Api14cSafeChartBuilderTest.

Method 7 — NORSOK P-002 Process Design Compliance

Screen flare/blowdown/vent hydraulics and drainage against NORSOK P-002 limits

with NorsokP002ComplianceChecker (fluent, aggregates all findings):

import neqsim.process.safety.compliance.NorsokP002ComplianceChecker;

NorsokP002ComplianceChecker c = new NorsokP002ComplianceChecker()
    .checkFlareLineMach("Header", 0.5)             // ≤ 0.7 Mach
    .checkBlowdownRhoV2("BDV-1", 150000.0)         // ρv² limit [Pa]
    .checkVentGasVelocity("Vent", 45.0)
    .checkLiquidCarryOver("V-100", 1.0e-4)
    .checkErosionalVelocity("Line-200", 80000.0)
    .recordDepressurisationValve("BDV-2", true, "Sized for fire case")
    .recordDrainSlope("CD-1", true, "1:100 slope OK");

boolean compliant = c.isCompliant();
int failures = c.countNonCompliant();
String json = c.toJson();      // findings tagged e.g. "FLARE_LINE_MACH_07"

Verified by NorsokP002ComplianceCheckerTest.

Method 8 — STS-0131 Technical Safety Gate

Aggregate the project safety acceptance checks (PSV margin, MDMT, SIL, custom)

into a single pass/fail gate with Sts0131Gate:

import neqsim.process.safety.compliance.Sts0131Gate;
import neqsim.process.safety.risk.sis.nog070.Nog070SifType;
import neqsim.process.safety.risk.sis.nog070.Nog070SilDetermination;

Sts0131Gate gate = new Sts0131Gate();
gate.addPsvSizingMargin(1.0, 1.15, 0.10);   // required, available, minMargin
gate.addMdmt(-20.0, -29.0);                 // operating MDMT vs design min
gate.addSil(Nog070SilDetermination.evaluate(Nog070SifType.PSD_PROCESS_SEGMENT, 5.0e-3));
gate.addCustom("Fire case", true, "Heat input within API 521 envelope");

boolean acceptable = gate.isAcceptable();
int failures = gate.countFailures();
String json = gate.toJson();

Verified by Sts0131GateTest.

Method 9 — Overpressure-Protection Study (TR3001 / API 521)

Use neqsim.process.safety.overpressure for a structured overpressure study on a

protected item: each cause calculator is fluent and returns an immutable

ReliefScenario; the engine picks the maximum-rate credible scenario, sizes

the PSV (vapour / liquid / two-phase), and checks acceptance against the ASME

VIII Div 1 accumulation limits (1.10 single non-fire, 1.16 multiple, 1.21 fire).

import neqsim.process.safety.overpressure.*;

// 1. Cause scenarios (fluent → ReliefScenario)
ReliefScenario blocked = new BlockedOutletRelief().setName("Blocked gas outlet")
    .setInflowRateKgPerHr(36000.0).setReliefPressureBara(50.0)
    .setReliefTemperatureC(20.0).setFluid(gas).calculate();
ReliefScenario fire = new FireCaseRelief().setName("Pool fire")
    .setVesselDiameterM(2.0).setWettedHeightM(3.0)     // or setWettedAreaM2(..)
    .setHasDrainage(true).setHasFireFighting(true)
    .setLatentHeatJPerKg(350000.0).setReliefPressureBara(60.0)
    .setReliefTemperatureC(120.0).setFluid(gas).calculate();

// 2. Engine: governing case + sizing + acceptance
ProtectedItem item = new ProtectedItem("V-100", 100.0)   // tag, MAWP [bara]
    .setReliefSetPressureBara(100.0).setBackPressureBara(1.5);
OverpressureStudyResult result = new OverpressureProtectionStudy(item)
    .addScenario(blocked).addScenario(fire).evaluate();

result.getGoverningScenario().getName();   // worst credible case
result.getRequiredAreaIn2();               // API 526 required orifice area
result.getRecommendedOrifice();            // orifice letter
result.isCapacityAdequate();               // area-based adequacy
result.getAcceptance().getAccumulationFraction();

// 3. TR3001 compliance findings (PASS / FAIL / NEEDS_REVIEW)
List<ComplianceFinding> findings = new TR3001ComplianceChecker().check(result);
boolean compliant = new TR3001ComplianceChecker().isCompliant(findings);

// 4. Disposal-header roll-up (API 521 §5.3)
ReliefDisposalResult disposal = new ReliefDisposalNetwork("Fire zone 1")
    .addRelief(resultA, true).addRelief(resultB, true).calculate();
disposal.getTotalSimultaneousKgPerS();
disposal.getPeakSingleKgPerS();
disposal.getGoverningContributor();

ControlValveFailureRelief, TubeRuptureRelief, FireCaseRelief.

them from governing-case selection.

governing case (SR-26503), capacity (SR-26506), acceptance (SR-26510), fire

basis (SR-26504), and dynamic determination (SR-26565); isCompliant is false

if any finding is FAIL.

TWO_PHASE (gasMassFraction, gasDensityKgPerM3, liquidDensityKgPerM3,

latentHeatJPerKg, liquidHeatCapacityJPerKgK) to trigger the matching sizing

path; missing two-phase inputs are reported as warnings, not failures.

not by re-plugging the selected area into the nozzle equation — API 520

empirical sizing and the nozzle capacity formula are not inverses.

header hydraulics. Verified by OverpressureProtectionStudyTest +

OverpressureExtensionsTest.

producers:** (1) *compare against existing/previous wells and inputs to the receiving

separator/header* — riser/inlet pressure, SIWHP, rates, choke dP, what the PSV/relief

basis was sized for, the ratio new versus historical, and the effect on the failed-open /

choke-collapse relief load; (2) *check blocked outlet as a function of current inflow, not

design inflow*, and state explicitly whether it governs. Today's lower production reduces

blocked outlet but not IVO+CC, so failed-open or choke-collapse is usually the governing PSV

case when the new source pressure exceeds earlier wells. Method, caveats and the

existing_wells_comparison results key are in neqsim-hp-lp-interface-overpressure (section 2b);

devtools/validate_task_results.py warns when the block is missing.

open the relief chapter with a scenario table (study status calculated / simple estimate /

qualitative, valve states, limiting mechanism, relief rate, governing or not), add an

installed-Cv input table (subsea and topside chokes intact and collapsed, riser EV, PV and its

maximum opening, PSV orifice and set pressure, stroke times, volumes) with source (document,

revision, page, or ASSUMED) and quality grade, and show a Cv sensitivity for failed-open AND

blocked outlet. Relief rates depend on the installed choke Cv, the actual dP and the stored

inventory; say what they depend on and what they do not. Method and results keys

(scenario_register, valve_cv_inputs, cv_sensitivity) are in

neqsim-hp-lp-interface-overpressure (section 2c); the validator warns when they are missing.

Common Mistakes

| Mistake | Fix |

| ---------------------------------------------------- | -------------------------------------------------------------------- |

| Counting BPCS twice as two IPLs | One BPCS = one IPL; control + alarm on same DCS = single layer |

| Claiming credit for procedural IPL with PFD 0.01 | Operator-action IPL minimum PFD = 0.1 (CCPS) unless trained+timed |

| Ignoring common-cause between IPLs | Same sensor / same final element ⇒ shared failure, halve credit |

| Setting target frequency = "fatality" | Use tolerable individual risk × exposed persons × outcome conditional |

| Picking SIL by "feel" | Always derive from LOPA gap (RRF needed) or risk-matrix calibration |

| Forgetting proof-test interval in PFD | PFDavg ≈ λ_DU × T_proof / 2; double T → double PFD |

Validation Checklist

Verification Tests

./mvnw test -Dtest=Nog070SilCatalogueTest,Sts0131GateTest,Api14cSafeChartBuilderTest,NorsokP002ComplianceCheckerTest,EsdResponseTimeSimulatorTest,OverpressureProtectionStudyTest,OverpressureExtensionsTest