NeqSim Flow-Accelerated Corrosion and High-Temperature pH Skill
Screening for flow-accelerated corrosion (FAC) — dissolution of the protective
magnetite film under mass-transfer control — and for the in-situ pH that
governs it.
When this skill applies
- Localised wall thinning or leaks at bends, elbows or circumferential welds
in carbon-steel tube bundles, with intact surfaces nearby.
- Closed heating- or cooling-medium loops (glycol/water or water),
boiler-feedwater, condensate, WHRU / economiser / steam-generator tubes.
- Operating temperature roughly 90–250 °C, peaking near 150 °C.
- Questions about pH control of an amine-buffered loop, or whether measured
chemistry is adequate.
Two mistakes to avoid before anything else
1. Do not judge a hot system by its laboratory pH.
Laboratory pH is measured on a cooled sample, typically at 20–25 °C. Corrosion
happens at 150 °C. Two things move, by different amounts:
- The amine pK$_a$ falls, so the buffered fluid becomes less alkaline.
- Neutrality itself falls: neutral water is pH 7.00 at 25 °C but about
pH 5.85 at 150 °C.
So the meaningful quantity is the alkaline margin, $\text{pH}(T) - \text{pH}_{neutral}(T)$,