Neqsim compressor antisurge recycle is an AI agent skill from the GitHub repository equinor/neqsim. Anti-surge recycle for centrifugal compressors in NeqSim: chart generation, AntiSurgeRecycleCalculator, dynamic AntiSurgeController, CompressorAntiSurgeApplication binding, MinimumSpeedRecycleControllerStructure split-range control, speed-solve convergence and recycle power/CO2 savings. USE WHEN: a

How to use this skill

Skill file

Compressor Anti-Surge Recycle Setup

This skill explains how to protect a centrifugal compressor against surge in a

NeqSim ProcessSystem by adding a recycle (spill-back) loop. It covers the

preferred steady-state helper (AntiSurgeRecycleCalculator), the dynamic

reverse-acting PI controller (AntiSurgeController), and the application-level

supervisor (CompressorAntiSurgeApplication) that can bind directly to real

NeqSim topology objects such as a compressor, hot recycle valve, cold recycle

valve, cooler, mixer, recycle blocks, and ProcessSystem. It also explains how

to auto-generate a compressor chart with surge and stonewall curves when no

vendor chart is available, because every anti-surge option needs a surge limit

to act against.

The pure-Python helper (AntiSurgeRecycleModel) is an educational planning aid

that mirrors NeqSim's proportional anti-surge step so an agent can pre-estimate

the recycle flow and decide whether a chart must be generated first. Real

control design must use the validated NeqSim equipment classes below and a

qualified rotating-equipment review (API 617 / API 692).

Complete compressor automation and P&ID studies

For a request to build a natural-gas compressor train with scrubbers, cooling,

anti-surge, instrumentation, shutdown tests and professional P&IDs, use the

agentic compressor workflow.

It coordinates the existing process, rotating-equipment, control, safety and

independent P&ID review agents. It requires an actual material graph, converged

steady state, canonical settings applied/read back on native copies, fault and

refinement tests, source-bound DEXPI 2.0.1/P&ID exports, and automation-engineering

registers/narratives. Proposed devices and direct compressor-derived inputs are

separate from executed measurement paths. A controller command alone is not

recycle-flow or surge-protection evidence.

For acceptance studies, use CompressorAutomationAcceptancePolicy and the

workflow's runWithAcceptancePolicy entrypoint. Retain the complete ordered

profile/criterion policy, its fingerprint and acceptance-study-summary.json.

Policy-only edits may change a verdict but must not change the physical sample

history; unknown identities, unit mismatches and incomplete policies fail closed.

When to Use

Use this skill when:

low throughput (turndown, start-up, trips) and needs recycle protection.

discharge splitter or recycle branch, anti-surge valve, Recycle, and

optional cooler/mixer).

CompressorAntiSurgeApplication writes hot/cold recycle valve openings and

optional compressor speed runback to real NeqSim units.

stonewall curves must be generated from the compressor's design point.

compressor off surge before running the full simulation.

Do not use this skill as a substitute for vendor performance maps, anti-surge

controller tuning, dynamic surge/transient analysis, or rotating-equipment

design review.

Inputs

is available, this comes from the generated surge curve.

optionally impeller diameter / number of stages for advanced corrections.

Outputs

Engineering Method

A centrifugal compressor surges when the inlet volumetric flow drops below the

surge flow at the current head/speed. Anti-surge control opens a recycle line

from discharge back to suction to keep the total suction flow above the

surge limit plus a margin.

For steady-state recycle sizing and initialization, prefer

AntiSurgeRecycleCalculator for a charted compressor. It runs the compressor,

checks natural inlet flow against the surge-control line, and iterates a cooled

recycle stream until the target distance-to-surge margin is met. Use the older

splitter-based Calculator / AntiSurgeCalculator pattern only when you need

to reproduce an existing flowsheet that already uses a discharge splitter.

The legacy splitter-based topology is:

  1. A surge curve on the compressor chart provides the surge flow versus head.
  2. A low-flow recycle stream is added into the compressor suction.
  3. A splitter on the compressor discharge creates a forward branch

(getSplitStream(0)) and a recycle branch (getSplitStream(1)).

  1. An anti-surge Calculator (legacy name-prefix API) or typed

AntiSurgeCalculator reads the compressor and writes the splitter recycle

flow each iteration. Internally it compares the inlet flow to the surge flow:

far from surge (inlet_flow > 1.2 * surge_flow) it drives recycle to a

minimum; otherwise it adds a proportional, capped step

0.5 * (surge_flow - inlet_flow) to the recycle branch.

  1. An anti-surge valve on the recycle branch drops the discharge pressure

back to suction pressure.

  1. A Recycle unit closes the loop, feeding the valve outlet back into the

placeholder suction recycle stream.

Generating a Compressor Chart When None Is Given

The anti-surge loop needs a surge limit, so if no vendor chart exists a chart

must be generated first. NeqSim builds a chart from the compressor's design

operating point and **automatically populates both the surge curve and the

stonewall curve**:

multi-speed chart whose lowest-flow points form the surge curve and whose

highest-flow points form the stonewall curve.

corrections, multistage surge correction, impeller diameter) and also returns

a chart with surge and stonewall curves attached.

After generation, the surge flow at the operating head is available through

Compressor.getSurgeFlowRate() and the distance to surge through

Compressor.getDistanceToSurge().

The AntiSurgeRecycleModel mirrors step 4 so you can estimate the recycle flow

and flag whether chart generation (needs_chart_generation) is required before

wiring the loop.

Python Usage Pattern

Screening estimate of the recycle flow (no NeqSim required):

from compressor_antisurge_recycle import AntiSurgeRecycleModel

model = AntiSurgeRecycleModel()
plan = model.plan(
    inlet_flow=4200.0,   # m3/h at suction
    surge_flow=5000.0,   # m3/h surge limit at operating head
    chart_provided=True,
    current_recycle=0.0,
)
print(plan.recommended_recycle_flow, plan.recycle_warning)

Generate a compressor chart (with surge and stonewall curves) when none is

given, using NeqSim through the neqsim package:

from neqsim import jneqsim

# `compressor` is an existing neqsim.process.equipment.compressor.Compressor
compressor.setSpeed(8000.0)   # design speed (rpm)
compressor.run()              # solve the design point first
compressor.generateCompressorChart("normal curves", 5)  # 5 speed lines

# Surge and stonewall curves are now populated automatically.
chart = compressor.getCompressorChart()
surge_flow = compressor.getSurgeFlowRate()
distance_to_surge = compressor.getDistanceToSurge()

Finer control with the generator (optional corrections):

from neqsim import jneqsim

generator = jneqsim.process.equipment.compressor.CompressorChartGenerator(compressor)
generator.setChartType("interpolate and extrapolate")
generator.enableAdvancedCorrections(numberOfStages)  # Reynolds + Mach + multistage
chart = generator.generateCompressorChart("normal curves", 5)
compressor.setCompressorChart(chart)

Wire the anti-surge recycle loop (generic data, after a chart exists):

from neqsim import jneqsim

splitter_pkg = jneqsim.process.equipment.splitter
valve_pkg = jneqsim.process.equipment.valve
util_pkg = jneqsim.process.equipment.util

suction_pressure = compressor.getInletStream().getPressure("bara")

# 2. Low-flow placeholder recycle stream into the compressor suction.
recycle_gas = compressor.getInletStream().clone()
recycle_gas.setName("anti surge recycle gas")
recycle_gas.setFlowRate(1.0, "kg/hr")
recycle_gas.run()
process.add(recycle_gas)

# 3. Splitter on the compressor discharge: branch 0 forward, branch 1 recycle.
gas_splitter = splitter_pkg.Splitter("anti surge splitter", compressor.getOutletStream(), 2)
gas_splitter.run()
process.add(gas_splitter)

# 4. Anti-surge Calculator (name MUST start with "anti surge calculator").
anti_surge_calc = util_pkg.Calculator("anti surge calculator 1")
anti_surge_calc.addInputVariable(compressor)
anti_surge_calc.setOutputVariable(gas_splitter)
process.add(anti_surge_calc)

# 5. Anti-surge valve on the recycle branch back to suction pressure.
anti_surge_valve = valve_pkg.ThrottlingValve("anti surge valve", gas_splitter.getSplitStream(1))
anti_surge_valve.setOutletPressure(suction_pressure, "bara")
anti_surge_valve.run()
process.add(anti_surge_valve)

# 6. Recycle unit closes the loop into the placeholder suction stream.
recycle = util_pkg.Recycle("recycle anti surge")
recycle.addStream(anti_surge_valve.getOutletStream())
recycle.setOutletStream(recycle_gas)
recycle.setTolerance(1e-2)
process.add(recycle)

process.run()

The forward process continues on gas_splitter.getSplitStream(0).

Preferred steady-state helper for a charted compressor:

AntiSurgeRecycleCalculator calc = new AntiSurgeRecycleCalculator(compressor, suctionStream);
calc.setSurgeControlMargin(0.10);
calc.setRecycleCoolerTemperature(35.0, "C");
AntiSurgeRecycleCalculator.Result result = calc.solve();

Constant-Speed Compressors: Fixed-Speed Operating Point

A motor-driven machine on a fixed gear (no VFD) cannot move speed, so the speed solvers of CompressorShaft do not

apply. Use CompressorShaft.evaluateFixedSpeedControl() (or `CompressorFixedSpeedControl.evaluate(compressor,

requiredBara)` for one stage). Per stage it reports, on the real chart at the fixed speed:

| Status | Meaning |

|---|---|

| ON_CURVE | chart delivers the required pressure at the process flow |

| RECYCLE_CONTROLLED | surplus head; recycle raises the through-flow until chart head = requirement; power, recycle fraction and discharge temperature are those of that point |

| THROTTLE_REQUIRED | surplus head even at stonewall; recycle cannot remove it |

| HEAD_DEFICIT | chart cannot reach the pressure (for example a lighter gas at the same flow); deliverableDischargeBara gives what it can |

Set the stage pressures with setMemberRequiredDischargePressure, call runAtFixedSpeed(rpm, null), then evaluate.

Idle members (1oo2 trains) are NOT_EVALUATED. The evaluation runs a deep copy of each member, so MW correction, IGV and

the efficiency model are those of the flowsheet. Tests: CompressorFixedSpeedControlTest.

Dynamic Anti-Surge Control (AntiSurgeController)

The Calculator-driven loop above is a steady-state recycle solver. For a

dynamic (transient) anti-surge response, NeqSim provides a dedicated

reverse-acting PI controller, AntiSurgeController

(neqsim.process.controllerdevice.AntiSurgeController), that reads

Compressor.getDistanceToSurge() and drives a recycle ThrottlingValve open as

the margin falls below the set point, then closes it again on recovery.

from neqsim import jneqsim

controllerdevice = jneqsim.process.controllerdevice

# `recycle_valve` is the anti-surge ThrottlingValve on the recycle branch.
asc = controllerdevice.AntiSurgeController("anti-surge", compressor, recycle_valve)
asc.setSurgeMarginSetPoint(0.10)   # protect a 10% distance-to-surge margin
asc.setProportionalGain(400.0)     # percent opening per unit margin error
asc.setIntegralTime(20.0)          # s
asc.setOpeningRange(0.0, 100.0)    # valve opening clamp (%) with anti-windup
asc.setActive(True)
recycle_valve.addController("anti-surge", asc)

Control law each transient step: error = setPoint - distanceToSurge,

integral += Kp/Ti * error * dt, opening = clamp(Kp*error + integral) with

anti-windup. A reproducible benchmark,

neqsim.process.util.scenario.AntiSurgeDynamicBenchmark, drives the real

controller against a transparent first-order gas-path surrogate

(m_next = m - disturbance*dt + authority*(opening/100)*dt) and is the preferred

way to verify or tune the control law without solver fragility.

Critical gotchas when building a full dynamic recycle flowsheet:

fraction** in dynamic mode, so the anti-surge valve has no authority over the

actual recycle flow — it can reach 100% open with no effect. Let the recycle

flow be set by the valve (Cv/resistance), or keep the steady-state

Calculator pattern.

getDistanceToSurge() clamps at -1.0 and the steady solver cannot recover;

a flowsheet driven into deep surge will not self-heal even after the inlet is

reopened. Apply gradual/ramped disturbances and keep the machine off deep surge.

starve a stream, and trigger an SRK flash NaN

(PhaseSrkEos:molarVolume ... NaN). Keep gains moderate.

Dynamic controller tuning and transient surge analysis still require qualified

rotating-equipment review (API 617 / API 692).

Application-Level Dynamic Topology Binding

For realistic dynamic studies with coordinated pressure, speed, hot recycle, and

cold recycle behavior, use CompressorAntiSurgeApplication. It is a

deterministic supervisory scan layer that can write directly to real NeqSim

objects and then advance the bound process one transient step.

CompressorAntiSurgeApplication application = new CompressorAntiSurgeApplication("export compression");
CompressorAntiSurgeApplication.StageApplication stage = application.addStage("K-101");

CompressorAntiSurgeApplication.TopologyBinding binding = stage.bindTopology(
  process,
  compressor,
  hotRecycleValve,
  coldRecycleValve,
  recycleCooler,
  suctionMixer,
  hotRecycle,
  coldRecycle);
binding.enableSpeedControl(95.0, 25.0, 8500.0, 12500.0, 150.0);

application.setRunningMode();
application.runDynamicStep(null, 0.25);

When the scan input is null, the stage reads the bound compressor margin and

inlet flow where available, falls back to the stage design basis where needed,

writes the hot and cold recycle valve openings, applies the optional compressor

speed command/runback, and advances the bound ProcessSystem with

runTransient(). Keep Recycle blocks algebraic unless the specific class has

transient inventory support; the valve, compressor, cooler, mixer, and any

volume-capable equipment carry the dynamic response.

CompressorAntiSurgeApplication is still a simulation and advisory layer. Its

certification status remains NOT_CERTIFIED_FOR_PROTECTION; use it for

engineering studies, training, digital twins, and commissioning evidence, not as

a certified machinery-protection package.

MCP `runProcess` Physical Topology Contract

Use two distinct JSON surfaces deliberately:

screening control. It does not create or certify a physical recycle path.

CompressorAntiSurgeApplication to named units that already exist in the

submitted process topology. It never synthesizes hidden valves, coolers,

mixers, or recycle blocks.

A single-area cold-recycle declaration has this shape:

{
  "autoSizing": {"enabled": true},
  "antiSurgeSystems": [
    {
      "name": "Export anti-surge",
      "stages": [
        {
          "name": "Stage 1",
          "compressor": "Comp",
          "suctionMixer": "Suction Mixer",
          "aftercooler": "Aftercooler",
          "coldRecycleValve": "Cold ASV",
          "coldRecycle": "Cold Recycle",
          "recycleDesign": {
            "controlMargin": 0.10,
            "valvePressureDrop": 10.0,
            "pipingVolume": 1.0,
            "requiredResponseTime": 5.0
          },
          "speedControl": {
            "dischargePressureSetPoint": 40.0,
            "minimumSpeed": 5000.0,
            "maximumSpeed": 15000.0,
            "speedGain": 40.0,
            "recycleRunbackRate": 80.0
          }
        }
      ]
    }
  ]
}

The referenced names must resolve to the expected concrete types:

Compressor, Mixer, optional Cooler, ThrottlingValve, and Recycle.

At least one complete hot or cold recycle path is required. For a multi-area

ProcessModel, every system also requires an area matching a submitted area;

unqualified and unknown-area definitions return bounded per-system failures.

Every stage needs an active surge curve. Supply properties.compressorChart,

enable autoSizing, or set generateScreeningMap: true on the stage. The

response reports truthful map provenance:

The latter two set screeningGradeMap: true. They are estimates, not vendor

maps. generatedScreeningMapCount counts all configured stages using a

screening-grade map, regardless of which generation path created it.

The response antiSurgeSystems object contains configured/failed counts,

per-stage physical binding and map provenance, optional speed-control status,

and runCommissioningChecks() evidence. Its certification status is always

NOT_CERTIFIED_FOR_PROTECTION. The canonical processDefinition preserves the

declaration, and the generated Python replays that canonical post-design JSON.

When a canonical response is replayed, its exported compressor chart is now an

explicitly submitted chart for that new request. Therefore its provenance is

submitted; replay does not generate another map. This makes JSON round trips

stable while preserving the original run's generation evidence in that run's

response.

Compressor Pressure-Target Solves

For Compressor.setSolveSpeed(true), check isSpeedSolveConverged() after run()

before accepting an optimization point. Read actual pressure from the outlet

stream and the signed pressure error in bar from getSpeedSolvePressureResidual().

getOutletPressure() retains the requested setpoint, including after failure.

The returned state uses the fixed-speed forward calculation, including anti-surge

flow changes; these can leave the requested pressure unmet. setLimitSpeed(false)

allows extrapolation, so pressure convergence does not establish mechanical

feasibility. Check speed and operating-envelope constraints separately.

ProductionOptimizer treats Compressor.SpeedSolveException as an infeasible

trial and continues searching without evaluating stale outputs; unrelated

exceptions propagate. Its hard compressorSpeedSolve constraint also rejects

returned unconverged results even with capacity analysis enabled. Keep this gate

when integrating chart-based compressor models into optimizers. See the

compressor curves guide

and CompressorSpeedSolveConsistencyTest for the tested contract.

Minimum-Speed Recycle Coordination (`MinimumSpeedRecycleControllerStructure`)

neqsim.process.controllerdevice.structure.MinimumSpeedRecycleControllerStructure

coordinates pressure control between compressor speed and recycle-valve opening when

the compressor reaches its minimum speed. Use it to stop opposing speed demand and

recycle-valve opening in a compressor pressure loop (control-optimization tasks).

  1. Split-range output: the pressure controller output is divided at a configurable

transition (e.g. 75 %).

  1. Speed command range: above the transition (75 % to 105 %) recycle addition is

zero and speed rises linearly from minimum (75 %) to maximum (100 %).

  1. Inverse recycle addition: below the transition (0 % to 75 %) speed is held at

minimum while recycle addition increases as pressure output falls.

  1. Latch on entry: on lower-range entry the previously selected recycle command is

latched and pressure-derived recycle is added to that baseline.

  1. High-selector protection: independent anti-surge and suction-pressure demands

join a high selector, $R_{selected} = \max(R_{latch} + R_{add}, R_{AS}, R_{suction})$,

so protection authority is never suppressed.

  1. Unwind before speed increase: on rising pressure, pressure-derived recycle

unwinds to the latched baseline before speed increases.

  1. Dynamic saturation floor: a lower output limit (latched * 74 / 100) prevents

integral windup.

import neqsim.process.controllerdevice.ControllerDeviceInterface;
import neqsim.process.controllerdevice.ControllerDeviceBaseClass;
import neqsim.process.controllerdevice.structure.MinimumSpeedRecycleControllerStructure;

ControllerDeviceInterface pressureController = new ControllerDeviceBaseClass("PIC-0205A");
ControllerDeviceInterface antiSurgeController = new ControllerDeviceBaseClass("UIC-0231");
ControllerDeviceInterface suctionController = new ControllerDeviceBaseClass("PIC-0131");

// (pressureCtrl, antiSurgeCtrl, suctionCtrl, transitionPct, maxOutputPct, minSpeedPct, maxSpeedPct)
MinimumSpeedRecycleControllerStructure coordStructure = new MinimumSpeedRecycleControllerStructure(
    pressureController, antiSurgeController, suctionController, 75.0, 105.0, 75.0, 100.0);

// In the transient loop or update step:
coordStructure.update(pressureControllerOutput, antiSurgeOutput, suctionPressureOutput);

double speedCommand = coordStructure.getSpeedOutput();             // % speed
double recycleAddition = coordStructure.getRecycleAddition();      // % recycle addition
double recycleCommand = coordStructure.getLatchedRecycleOutput();  // % latched baseline

Energy and CO2 Savings from Avoided Recycle

When recycle opens uncoordinatedly while the compressor runs at minimum or elevated

speed, extra gas is re-compressed without increasing net forward production.

  1. Shaft power: $P_{shaft} = \dfrac{\dot{m}_{net}\, h_{poly}}{\eta_p (1 - \alpha_{recycle})}$,

with recycle fraction $0 \le \alpha < 1$.

  1. Power penalty: $\Delta P = P_0\,\dfrac{\alpha}{1 - \alpha}$.
  2. Fuel and CO2: $\Delta \dot{m}_{fuel} = \dfrac{\Delta P}{\eta_{driver}\,LHV}$ and

$\Delta \dot{m}_{CO2} = \Delta \dot{m}_{fuel}\, e_{CO2}$.

  1. Annual saving (MNOK/yr) $= \dfrac{\Delta m_{CO2,yr}\,\mathrm{Tax}_{CO2} + \Delta m_{fuel,yr}\,\mathrm{Value}_{gas}}{10^6}$.

Recipe: build the recompressor with a fixed net feed, then sweep the recycle fraction

by setting the suction flow to net / (1 - alpha) and re-running stream and compressor;

the power difference to $\alpha = 0$ is the penalty. Quantify annual MWh, fuel-gas

tonnes, CO2 tonnes and cost over the operating hours, and compare the dynamic

pressure, speed, recycle, power and CO2 time series.

Fixed Minimum Flow Without a Numerical Recycle Loop

For steady-state screening with a prescribed minimum suction flow and a return cooled

to the net-feed suction state, use

neqsim.process.equipment.compressor.MinimumFlowSpill(name, netFeed).

Set setMinimumInletFlow(value, unit) and configure getCompressor().

Add the assembly once to the ProcessSystem; the net forward outlet is

getOutletStream(), while getSpillStream() is an internal discharge spill.

getSpillFlow(unit) uses suction conditions even for actual volume.

Use getPower(unit) for gross compression and getSpillCoolingDuty(unit) for

ideal heat rejection. The assembly delegates capacity constraints to its compressor.

Disable internal AntiSurge flow modification. Use physical valve, cooler and recycle

equipment for composition changes, condensation, finite cooler approach or dynamics.

See the compressor equipment guide

and MinimumFlowSpillTest for the executed synthetic material and energy checks.

Validation Checklist

if not, generate one and confirm getSurgeCurve().isActive() is true.

practical; if using the legacy splitter path, the anti-surge Calculator name

starts with "anti surge calculator" or the typed AntiSurgeCalculator is

used.

the output is the discharge Splitter.

intended margin (getDistanceToSurge() is positive).

are real ThrottlingValve units, speed-control limits are bounded, and

runDynamicStep(...) is used only after the process has a converged initial

state.

physical units are present in process; require area for every multi-area

system and inspect configuredCount, failedCount, mapProvenance,

screeningGradeMap, commissioning checks, and certification status.

Common Mistakes

Fixed-speed chart calculations reject nonfinite or negative head and efficiencies

outside (0, 100] percent before the PH flash. If this diagnostic appears, check

actual inlet flow, speed, and map range; do not treat polynomial extrapolation to

negative map values as a thermodynamic solver failure or clamp it into feasibility.

CompressorChartOperatingPointTest covers rejection and accepted-outlet preservation.

"anti surge calculator" — the legacy anti-surge logic then never triggers.

of the recycle branch getSplitStream(1).

against (generate a chart first when no vendor chart is given).

converge from; start from a small positive flow (for example 1 kg/hr).

the operating head and speed.

estimates for modelling, not design certification.

the AntiSurgeController valve has no authority over the recycle flow.

getDistanceToSurge() clamps at -1.0 and the steady solver cannot recover.

CompressorChart fits one quadratic of H/N^2 vs Q/N through all speed lines,

which on a real vendor map shifts discharge pressure by 10-15 % at the outer

speed lines (and moves the surge flow with it). Call

compressor.setCompressorChartType("interpolate and extrapolate") BEFORE

getCompressorChart().setCurves(...); Pump.setPumpChartType(...) has the same

option. Units for setCurves: actual inlet m3/hr, head kJ/kg or meter,

polytropic efficiency in PERCENT.

The default method uses xT = 0.137 without choking and under-rates a globe

anti-surge valve by a factor ~2 at pressure ratio 4. Set

getMechanicalDesign().setValveSizingStandard("IEC 60534"), then on

getValveSizingMethod() call setxT(0.70), setFL(0.90) (or the vendor's

values) and setAllowChoked(True) before setCv(cv, "US").

write-up. Vendor controllers store the surge-control line as a function

generator in (Q^2, DP/Ps) coordinates; the flow margin is

sqrt(Q^2_SCL / Q^2_SLL) - 1 at equal DP/Ps (~20 % in Q^2 = ~10 % in flow is

typical), then compressor.setSurgeControlMargin(margin).

Limitations

recycle valve Cv, response time, or surge control line offset.

analysis; for dynamic response use NeqSim's AntiSurgeController /

AntiSurgeDynamicBenchmark under qualified review.

Multi-Body Compressor Trains on One Shaft (common speed)

When several compressor bodies sit on one driver shaft (a single gas turbine

or motor, often through a gearbox) they must all turn at the same speed. A

2- or 3-body recompression string is the classic case. Model it with

neqsim.process.equipment.compressor.CompressorShaft, NOT by letting each body

solve its own speed.

Degrees of freedom. A shared shaft has exactly one mechanical degree of

freedom — the common speed — and exactly one controlled target: the string's

final discharge pressure. Every intermediate inter-body pressure is a

result, not a spec, and must be allowed to float off the charts.

| Approach | DOF accounting | Verdict |

|---|---|---|

| Fix every stage outlet pressure and set a common speed | over-constrained | ❌ non-physical |

| Adjust ONE common speed → hit the final discharge; intermediates float | 1 variable, 1 target | ✅ correct |

Pattern. Put each body in fixed-speed, chart-forward mode and iterate the one

common speed until the reference (last) body hits the target discharge:

CompressorShaft = jneqsim.process.equipment.compressor.CompressorShaft
shaft = CompressorShaft("recompression shaft (single GT)")
shaft.addCompressor(body1)   # LP body (lowest suction)
shaft.addCompressor(body2)
shaft.addCompressor(body3)   # HP body = reference
shaft.setSpeedBounds(8000.0, 16000.0)
# re-run the whole flowsheet between speed guesses so inter-body streams,
# scrubbers and mixers update:
run_proxy = jpype.JProxy("java.lang.Runnable", dict(run=lambda: process.run()))
shaft.solveSpeed(body3, 49.0, "bara", run_proxy)   # one speed -> 49 bara at HP discharge
rpm = shaft.getSpeed()
mw = shaft.getTotalPower() / 1e6

Shared pressure nodes. Where another unit ties into an interstage (e.g. a

2nd-stage separator gas that joins the recompressor between bodies), model it as

a pressure equality, not a second spec: slave that unit's pressure to the

floating interstage discharge (a setter each iteration) or drop a small adapting

valve there. This removes a DOF rather than adding one. A Mixer at the join

already resolves to the lowest inlet pressure, so a small let-down is automatic.

Fixed-/single-speed drivers. If the driver is a constant-speed motor (no

variable-speed drive) speed is not a DOF — do not iterate it. Use

shaft.runAtFixedSpeed(rpm, run_proxy): the discharge floats off the chart at

the locked speed and any pressure spec is met by anti-surge recycle, suction

throttling, or inlet guide vanes — never by moving speed. Inlet guide vanes are a

first-class fixed-speed control on Compressor:

comp.setInletGuideVaneOpening(f) (f=1 fully open) or comp.setGuideVaneAngle(deg)

closes the vanes to reduce head and efficiency and lower the surge flow (via a

configurable InletGuideVaneModel), so getDistanceToSurge() reflects the shifted

surge line — distinct from moving speed. If you have vendor IGV-position maps

(a full chart per vane position), attach a CompressorChartIGV family with

comp.setInletGuideVaneChart(family); it interpolates the positions into the active

chart at each opening (and bypasses the parametric model). Use the parametric

InletGuideVaneModel for screening / fixed-speed discharge control, and

CompressorChartIGV to supply real per-position vendor maps.

Single body. A CompressorShaft with one compressor also works: solveSpeed

just finds that one machine's speed for its discharge target. So export /

re-injection / gas-lift machines (one body each on their own shaft) use the same

API — separate shafts keep separate speeds.

Anti-surge coexists. The per-body anti-surge loops (recycle splitter, valve,

Recycle, AntiSurgeCalculator) stay attached and keep protecting each body;

they adjust recycle flow, while the shaft sets speed. Apply the shaft solve

after the charts and anti-surge are active. solveSpeed uses a bracketed

false-position (Illinois) secant — the speed↔discharge map is smooth and

monotonic (higher speed → higher discharge), so it converges superlinearly. Each

iteration re-solves the whole flowsheet, so on a large multi-train plant make the

shaft solve opt-in and solve each train's shaft in turn.

Parallel machines and multi-stage strings. Real duties often use two parallel

bodies (A/B) rather than one machine: split the feed 50/50, give each body its own

anti-surge loop, and commingle with a Mixer. Splitting one large machine into two

halves the per-machine gas load (a suction scrubber that reads ~168 % of design on

one body drops to ~80 % on two). For a multi-stage duty (e.g. re-injection),

commingle the parallel 1st-stage discharges then feed a common 2nd stage at an

interstage pressure. Route a recompression train's HP discharge back to the gas

header, not straight into the export suction.

Process-integrated control (CompressorShaftCalculator). Instead of the

external solveSpeed callback, add a CompressorShaftCalculator to the

ProcessSystem; it converges the one common speed inside process.run()

(one damped secant step per pass, like AntiSurgeCalculator) so the shaft speed

converges together with the recycles in a single run — no separate full-field

solves. Add it after the compressor bodies / anti-surge.

CompressorShaftCalculator = jneqsim.process.equipment.util.CompressorShaftCalculator
shaft = CompressorShaft("recompression shaft (single GT)")
shaft.addCompressor(body1); shaft.addCompressor(body2); shaft.addCompressor(body3)
shaftCalc = CompressorShaftCalculator("shaft speed", shaft, body3, 49.0, "bara")
shaftCalc.setSpeedBounds(8000.0, 16000.0)
process.add(shaftCalc)
process.run()          # shaft speed converges with the recycles
rpm = shaftCalc.getSpeed()

Feasibility result + pressure control (eCalc-style). A single-speed string

cannot make an arbitrary pressure — the max-speed curve is a ceiling and the

min-speed curve is a floor. Both solvers saturate and flag instead of

crashing, and expose a CompressorShaft.SolveResult (read with

getLastSolveResult(), or the shortcut isFeasible()). The two speed-bound

bracket evaluations give the min-/max-achievable discharge pressures for free.

shaft.solveSpeed(body3, 49.0, "bara", run_proxy)
r = shaft.getLastSolveResult()
if not r.isFeasible():
    # r.getStatus(): PRESSURE_ABOVE_MAX_SPEED / PRESSURE_BELOW_MIN_SPEED / OVER_POWER / STONEWALL / SURGE
    ceiling = r.getMaxAchievablePressure()   # most the string can make
# too-low target -> shed the surplus head instead of flagging infeasible:
PressureControl = jneqsim.process.equipment.compressor.CompressorShaft.PressureControl
shaft.setPressureControl(PressureControl.DOWNSTREAM_CHOKE)   # or UPSTREAM_CHOKE / ASV_RECYCLE

CompressorShaftCalculator carries the same getLastSolveResult() /

isFeasible() / setPressureControl(...), so an optimizer or evaluate() loop

can gate on shaftCalc.isFeasible() directly. Downstream, Mixer.isPressureMismatch()

flags where an unmet pressure collapses a commingling node to the lowest inlet —

the signal that an upstream machine missed spec. A worked end-to-end example

(three-stage separation + shared-shaft recompression + control) is in the NeqSim

repo notebook examples/notebooks/CompressorShaft_ThreeStageSeparation.ipynb.

Common-Shaft Trains Across Platforms, Power-Limited Drivers and Ambient Derating

CompressorShaft (since 3.26) covers the cases a plain "one shaft, one target" model misses. All of it is

reached through the same object, and the members may live in different ProcessSystems (the

Runnable you pass to solveSpeed runs every system in order and copies the inter-platform stream).

shaft = CompressorShaft("HT 3rd+4th+5th stage (one GT)")
shaft.addCompressor(ka23003)            # OSA, ratio 1.0
shaft.addCompressor(ka23004, 1.0)       # OSD; second argument = gear ratio (member rpm per shaft rpm)
shaft.addCompressor(ka26001, 1.2)
shaft.setSpeedBounds(rpmMin, rpmMax)    # driver speed band; keep it inside the chart-valid region
shaft.setGasTurbineUnitDriver(gt)       # site-rated GasTurbineUnit (power vs ambient, exhaust-T limit)
shaft.setAmbientTemperature(24.0, "C")  # moves the driver rating; also feeds a CompressorDriver
shaft.setMemberRequiredDischargePressure(ka26001, 160.0, "bara")   # margins in the report
# controlling member sets the speed; the others float on their charts at r_i * N:
shaft.solveSpeedToTarget(ka23003, CompressorShaft.ControlTarget.DISCHARGE_PRESSURE, 24.0, "bara", run_both)
# other targets: SUCTION_PRESSURE (bara) and INLET_FLOW ("kg/hr" or "m3/hr"); direction is not assumed
report = shaft.getOperatingReport()     # per member: speed, power, surge/stonewall distance,
                                        # requiredRecycleFraction (to control line), flags; JSON via toJson()

flow and discharge-pressure target; the 4th/5th stage run at the same speed, their flow follows from the

process, and the report gives the margin to the discharge need ("excess head (throttle or recycle)",

"speed too low for the discharge need") and the recycle fraction anti-surge must carry

(requiredRecycleFraction, recyclePowerW). After the 3rd stage gets its own motor (DG4), call

shaft.removeCompressor(ka23003) and give it a new CompressorShaft with setMaxShaftPower(5, "MW") or

setElectricSupplyLimit(MW, "MW", motorEff).

year) in a table, run each part with its own shaft set and report the time weight. Details, the efficiency-calibration

and chart-similarity pitfalls: neqsim-rotating-equipment-design, section "Chart gas similarity, efficiency

calibration and chart-speed basis".

from the power sum and limit checks; with no active member solveSpeed returns 0 rpm and status

SHAFT_IDLE (feasible). The idle compressor's outlet is not updated, so give an idle train a bypass line or

zero flow in the flowsheet.

else GasTurbine rating, else GasTurbineUnit.getAvailablePowerAtAmbient(T); setElectricSupplyLimit

caps it by the smaller value. solveSpeed flags OVER_POWER; findMaxSpeedWithinPowerLimit(run) gives the

highest speed the driver holds; `DriverLimitedThroughputSolver(shaft, ref, targetP, "bara", flow -> ..., run)

.solve(minFlow, maxFlow) gives the highest throughput and the binding limit (DRIVER_POWER, MAX_SPEED`,

SURGE, STONEWALL, NONE).

shaft demand; read getFuelMassFlowKgPerHr(), getExhaustTemperatureK(),

getWasteHeatRecoveryDutyW(stackK, effectiveness).

so set speed bounds inside the chart-valid region; the discharge-pressure solve of one member assumes

pressure rises with speed (suction/flow targets only need a bracket). Details and the gap list:

neqsim-rotating-equipment-design section "Compressor trains on a common shaft".

(1) Do not take gear ratios from datasheet rated speeds. The digitised charts of KA23003 and KA23004 share one speed grid

(70-108 % of 10200 rpm) and neither reproduces its Hatch rated speed (10037 / 10710 rpm); the effective member rpm per

power-turbine rpm, read from measured pressure / temperature / recycle-inclusive flow, was 2.18 for both - one ratio, not 0.937.

Derive the ratio per machine from a measured window (required_member_speed), keep the other window as a check, and read an

ASV-recycled machine at its machine flow (net flow x measured recycle), not at the net flow.

(2) The controlling member sets N only while it needs the highest speed. A follower that must reach its discharge pressure

above its surge control line imposes a minimum speed; use N = max(N_control, N_min,follower) (min_shaft_speed_on_control_line)

and report which one binds. Followers have no flow target: their flow is the chart flow at N (capacity), the surplus is

recycled / let down, a shortfall is a surge or stonewall flag.

(3) A controlling member below its control line is held on it by the ASV: evaluate its head at max(Q, Q_surge (1 + margin))

or its speed demand is understated by 10-15 %.

(4) Keep the flow of a follower out of the solve. If the follower flow is an input (table or measured recycle), the shaft

speed only checks it; to make the volume an output, drop the measured recycle and iterate N and the flow in the outer loop.

(5) Loop gain across platforms. A recycle of flash gas between two coupled simulators (NGL stabiliser -> LP compression -> DPC

-> stabiliser) can amplify; compare the one-way coupled result with the converged loop before blaming the composition.

(an under-loaded train - net flow small against surge - is read at its machine flow, and its speed is then set by the 4th stage).

Related NeqSim Functionality

compressor bodies on one shaft at a single common speed;

addCompressor(...), solveSpeed(reference, targetP, unit, runnable) (iterate

one speed to the final discharge, intermediates float),

runAtFixedSpeed(rpm, runnable) (constant-speed drivers), setSpeed(...),

setSpeedBounds(...), getSpeed(), getTotalPower().

generateCompressorChart(...), getCompressorChart(),

getSurgeFlowRate(), getDistanceToSurge(), setSpeed(...).

getSurgeCurve(), getStoneWallCurve(), generateSurgeCurve(),

generateStoneWallCurve(), checkStoneWall(...).

setChartType(...), enableAdvancedCorrections(...),

generateCompressorChart(...).

steady-state recycle helper for charted compressors

(setSurgeControlMargin, setRecycleCoolerTemperature, solve).

application-level supervisor with StageApplication.bindTopology(...),

TopologyBinding.enableSpeedControl(...), scan(...), and

runDynamicStep(...) for direct writeback to real hot/cold recycle valves and

compressor speed.

and recycle branches.

(runAntiSurgeCalc) triggered by the "anti surge calculator" name prefix.

PI controller on getDistanceToSurge() driving a recycle valve

(setSurgeMarginSetPoint, setProportionalGain, setIntegralTime,

setOpeningRange, setActive).

surrogate benchmark for verifying/tuning the dynamic control law.

The total_suction_flow (net forward flow + recycle) computed here is the

actual compressor throughput. When you go on to compute polytropic

head/efficiency or shaft power from measured conditions, use this actual

throughput — not the metered net/export flow. Using net flow while the recycle is

open understates suction volume and power and mis-locates the operating point on

the surge map (a common error when diagnosing compressor degradation at

turndown).

In Python these classes are reachable through the neqsim package (for example

from neqsim import jneqsim).

References